incinerator type of pyrolytic medical waste incinerator capacity

Including:Incinerator: Structure to be specified
The mark to be specified
Water temperature: 800 to 1000 ° C;
Refractory
Temperature of more than 1100 ° C + obtained;
Capacity: 20-50 kg / hour
Fireplace: 4 to 6 meters high;
Dimension 70 cmx70 crn
Height: 1.10 meters
Fuel: coal;
Aspiration: natural

– A receiving cage for biomedical waste;

– A combustion chamber with a chimney with a filter to retain the ashes;

Chimney section: about 300 cm; With a minimum height of 6 m

Door size: approximately 50×60 cm

Supplied with a 500 liters fuel tank and all necessary accessories for installation.
–                          INCINERATOR for pharmaceutical waste treatment with                  a scrubbing system

With the following technical data:

1.      One pharma solid waste incinerator unit containing two combustion chambers and based on steel base with scrubbing

system.

2.      Working hour /day: minimum 10 hours/day.

3.      Capacity: Approximated 150 kg/hr. Over 10 hrs.

4.      Wastes characteristics:

·         BULK density: 70 – 100 kg/ bm³.

·         Calorific value: 2000-3000 kcal / hr.

·         Moisture content: 20-30%by weight.

·         Ash content: 2 – 8 % by weight.

·         Plastic content: 15-20 % by weight.

5.      Two combustion chambers.

6.      Operating temperatures:

·         First chamber: not less than 700 – 800 °c.

·         Second chamber: not less than 1200 °c (during steady operation).

7.      The burners should be automatically switched off if any of the combustion chambers doors is open.

8.      The burners of the first and second combustion chambers are selected for burning diesel oil (light fuel).

9.      Automatic loader and unloader to be provided.

10.     Exhaust gases to be comply with International Environmental code and requirements.

diesel oil fired medical waste incenerator

High Temperature Waste Incinerator Model D. MB 750XL Burn Rate-150Kg/hour minimum Weight(Kg)-4000kg Secondary Chamber

(double chamber with post-burning) Gas Retention Time 2 second Fuel Diesel Power Supply for control box 220V-240, single

phase 50-60Hz Minimum operating temperature 1200 oC One year spare parts package for complete maintainability 10m hose

pipe. 1100 litre fuel Tank +pipe system Containerised (the container will serve as housing) Additional chimney extension

1 metre high One (1) year warranty.

Incinerator of 20 Kg : 03 Units

Electrically controlled incinerator.

Two-compartment incinerator with a capacity of 20 kg / hour.

Incinerator with low maintenance and operating costs; Equipped with an automatic control panel and easy to use with

electromagnetic locking of the door.

A main waste reduction chamber of 900 ° C. A post secondary combustion chamber of gases generated in the primary chamber

at least 1100 ° C.

Carbon residues in ash less than 5% by weight in accordance with European Directive 2000/76 / EC.

With refractory lining in materials of higher quality
1/ Cost of a 200kgs/Hr medical waste incinerator.
2/ (CIF Term) Cost of shipping from factory to PAPUA NEW GUINEA seaport of LAE, Morobe province
3/ Cost of 2 Clover engineers to Supervise, Installation, Training our engineers and commissioning the medical; waste

incinerator.

manufacturer of ha zardous waste incinerator in china

Burning Capacity: 125 kg minimum/time (3-6times/day), double chamber, double combustion system
Imputing door Mouth Width (mm): 760*760 (approx.)
Chimney External Diameter (mm): 300 ± 10
Combustion Improver Device: 0.11kw, Fuel consumption: 7kg/ hour (max)
Re-Burning Device: Oil consumption: 5kg/h, 0.37kw, Oil consumption: 10-20kg/h
Voltage: 380v/220v AC, Warranty: 1 Year, 50 Hz

Per your advertisement for 300 kg.hr. Model – We need to know the price via return.

How many Kg. of Fuel would be required for running this Model 10 hrs. everyday.

We have our own Freight Forwarding Agent.

We had a Contract for Garbage Management before their Civil War for 120 Tons/Day for one Municipality in North Africa
Medical Waste Incinerator

Dual Chamber (Primary & Secondary) with insulation slabs (fully insulated internal refractory lining) along with

controlled air blower for each chamber

Insulation / Refractory Thickness: ≥ 100mm

Chamber plate thickness: ≥ 6mm

Fuel Type: Natural gas based on burning fuel in combustion chambers

Waste Capacity: ≈ 150 Kg/Day

Incineration capacity: ≈ 25 Kg/Day (Separate waste charging and waste removal doors)

Burners: At least with (02) burners of automated start and stop functions

Combustion efficiency: > 97%

Temperature: programmable temperature with temp monitoring system

Residence time: 2 second in secondary chamber

Heating value: 4000 Kcal

Temperature Range: ≈ min 800ºC to max 1200ºC

Electrical supply: 220V with single phase

Chimney Plate Thickness: ≥ 5mm

Water scrubber: Scrubbing using reagent like lime & should made of SS 10 gauge of non-corrosion properties and painted

exteriorly by equipment grade heat resistive enamel

Chimney Height: between 15-25 feet

portable medical waste incinerator manufacture companies in china

Capacity: 20KG/Hr, Temp Range: 600 Deg. C – 1100 Deg. C

Fuel Supply: Natural Gas/Diesel

Dual Combustion Chamber Complete Scrubbing System (Dual

Resultant Gas Washer), Dual Blower, Chimney Height: 8m

Electric Supply: 220/240Volt, Single Phase

1.    Type of waste: Trash
2.    Any other type:
3.    Quantity of waste generated per day in kg: (50 Ton per day) SOW
4.    Duration – incinerator will be used per day: (Minimum 12 hours) SOW
5.    Approximate moisture content:
6.    Local incinerator operating and emission standards: US-EPA
7.    What is the height of the chimney required: Not known
8.    Fuel proposed to be used: Deiseal Oil
9.    Availability of power and type: 220 or 110
10.    Details of space available: Plenty of space
11.    Do you require an automatic loading system: [**] Yes  [**] No
12.    Do you require a gas scrubbing system: [**] Yes  [ ] No
13.    How soon do you require the system to be delivered: 30
14.    Any other specific requirements:
15.    Nature: (Solid/Semi-solid/Liquid)

infectious waste pyrolysis machine chinalarge animal incinerators

Major components are – Ethanol, Paraffin, Silicon, Aluminium chloro hydrate, Bentone ,LPG

quote for incinerators for industrial chemical wastes treatment,

1 burning rate must be Average 30kgs\h
2 inside of chamber material must be refractory concrete cement
3 it works in three system diesel oil\ Natural gas or LPG
4 voltage must be 220V

5 inside temperature first must be 1000c  and second must be 1200c
6 pipe length must be 20 M

Our requirements are  for 125 kg/hr and 42 kg/hr, please send quote with catalog for both options
We are currently dealing in Defense Related Equipment, Construction Assistance and Medical Equipment, Modular Solutions

for Hospitals, Waste Management System, CSSD, Hospital Furniture and Services. We are based in the Capital city of

Pakistan i.e. Islamabad ,where there are all the head offices of Military and Govt. institutions. We have the capacity to

Participate in tenders and we also have a strong network of energetic/active dealers and sales staff in Pakistan and

Afghanistan.
5 incinerator 15 kg the specifications High temperature incinerator​99% combustion efficiency Temperature up to 1200°C or

Smoke and smell free Excellent heat retention Electric powered​ Fast heatup times Temperature Up to 1200°C or as required

Capacity​15 Kg Burning Efficiency 98% Noise- <78db Power – Electric Chamber​Single / Dual chamber Safety Alarm Emergency

vent Monitoring device​ Air Pollution Control Device​ CE and ISO Certified

I ‘d like to ask you about a power plant by burning waste. We have many of camps for displaced people in Syria, and we

want to buy a plant to generate electricity by municipal waste incineration Please send me an offer or any details.

low-cost medical waste incinerator

Stack:
Type:  Wire Supported
MOC:  Mild Steel of ISstd
Height :3 Meters or more
• PROCESS AT LEAST 1 METRIC TON OF WASTE PER DAY
• OPERABLE BY 1 PERSON, WITH NO TRAINING REQUIRED
• REGULAR MAINTENANCE CAN BE COMPLETED BY 1 PERSON WITH LIMITED TRAINING
• REGULAR MAINTENANCE SHOULD NOT EXCEED 1-HOUR PER DAY
• COMPLIES WITH EURO / OR US-EPA EMISSION STANDARDS
• ABILITY TO INCINERATE WASTE PETROLEUM, OILS, AND LUBRICANTS
• TEMPRATURES DURING THE COMBUTION PROCESS MUST EXCEED 1,500 °F FOR AT LEAST 1-HOUR
• CAN BE TRANSPORTED TO AND FROM DEPLOYMENT LOCATION IN A 20-FOOT OR SMALLER SHIPPING ISO CONTAINER
• CAPABLE OF 24 HOURS OF CONTINUOUS USE
• AUTOMATIC LOADING SYSTEM
• AUTOMATED ASH REMOVAL SYSTEM
• GAS SCRUBBING SYSTEM
• 95% REDUCTION OF SOLID WASTE
• OPERABLE WITH DIESEL, JP8, OR FUEL OIL
• CAPABLE OF BURNING 4 UNITS OF WASTE PER UNIT OF FUEL
• ABLE TO INCINERATE COMBUSTIBLE WASTE TO INCLUDE: PAPER, PLASTIC, CARDBOARD, FOOD, USED OILS, SLUDGE, OILY RAGS, AND

WOOD PALLETS.
• NO PRE-TREATMENT OF WASTE REQUIRED
• VENDOR REPAIR OFFERED AT POINT OF SHIPMENT
• FIVE (5) YEAR COMPONENT WARRANTY FROM DATE OF ACCEPTANCE
We are an aerosol manufacturing company.. Our products includes Deodorants, Anti perspirant deodorants ,air freshners,

Insect killers etc..

china incinerator manufacturer and exporter

Primary Combustion Chamber
Waste Charging Door: Provided with refractory lining with sealing gaskets
Ash Removed Door: Provided with refractory lining with sealing gaskets
Outer Body MOC: Mild Steel, 5mm
Primary Chamber: Stainless Steel
Operating Temperature :800. ± 50◦C
Insulation: Insulation Brick
Heating Elements Type: Kanthal Al Grade
Power Consumption: 75 KW ( Initial Load )
Electrical Supply :3 Phase 440 Volt
Control Panel
MOC: Mild Steel Power Coated
No. of Temp: Controllers : 2 Nos
Details: The Control Panel will be provided with contract as relays , switches , indicators etc . Operative on 3 phase.
I.D.Fan
Type: Centrifugal Type
MOC: Mild Steel
Capacity:2 HP/3Phase
Make of Motor: Kirloskar /Havells/Crompton
Combustion Air Fan
Type: Centrifugal Type
Capacity: 1HP/3Phase
Make of Motor: Kirloskar /Havells/Crompton